1. Standard Voltage Drop Formulas
Single-Phase AC & DC: Vdrop = 2 × L × I × R ÷ 1,000. Three-Phase AC: Vdrop = 1.732 × L × I × R ÷ 1,000. Always measure L as one-way conductor run length in feet.
THE TOOLBOX / LIFE & ELECTRICAL SIZING
Compute exact voltage drop, delivered load voltage, conductor heat loss, and minimum compliant Copper or Aluminum AWG wire size for 120V/240V branch circuits, subpanels, 3-phase motors, and 12V DC solar/RV runs.
UPSIZE RECOMMENDED: Switch to at least 8 AWG copper to stay under 3% voltage drop and within 75°C ampacity.
| Gauge | Drop (V) | Drop (%) | 75°C Amps | Status |
|---|---|---|---|---|
| 18 AWG | 23.31 V | 19.42% | 14 A | Upsize |
| 16 AWG | 14.67 V | 12.22% | 18 A | Upsize |
| 14 AWG | 9.21 V | 7.68% | 20 A | Upsize |
| 12 AWG | 5.79 V | 4.83% | 25 A | Upsize |
| 10 AWG | 3.63 V | 3.02% | 35 A | Upsize |
| 8 AWG | 2.29 V | 1.91% | 50 A | ✓ Pass |
| 6 AWG | 1.47 V | 1.23% | 65 A | ✓ Pass |
| 4 AWG | 0.92 V | 0.77% | 85 A | ✓ Pass |
| 2 AWG | 0.58 V | 0.48% | 115 A | ✓ Pass |
| 1 AWG | 0.46 V | 0.39% | 130 A | ✓ Pass |
| 1/0 AWG | 0.37 V | 0.30% | 150 A | ✓ Pass |
| 2/0 AWG | 0.29 V | 0.24% | 175 A | ✓ Pass |
| 3/0 AWG | 0.23 V | 0.19% | 200 A | ✓ Pass |
| 4/0 AWG | 0.18 V | 0.15% | 230 A | ✓ Pass |
NEC WIRE SIZING GUIDE
Single-Phase AC & DC: Vdrop = 2 × L × I × R ÷ 1,000. Three-Phase AC: Vdrop = 1.732 × L × I × R ÷ 1,000. Always measure L as one-way conductor run length in feet.
A wire must satisfy two checks: safe 75°C thermal ampacity (so insulation never overheats) AND ≤3% branch voltage drop (so motors, EV chargers, and inverters run efficiently).
Continuous 48A EV chargers on a 60A breaker over 75–100 ft frequently benefit from upsizing from 6 AWG to 4 AWG copper to cut continuous heat waste inside walls and conduit.
Planning an electrical project? Check our Conduit & Box Fill Calculator, Electricity Cost Calculator, Ohm's Law & Voltage Divider, or Unit Converter.
| Wire Size | Copper Resistance (Ω / 1,000 ft) | Copper 75°C Ampacity | Common Residential / DC Use |
|---|---|---|---|
14 AWG | 3.07 Ω | 20 A (15A breaker) | 15A lighting & bedroom receptacles |
12 AWG | 1.93 Ω | 25 A (20A breaker) | 20A kitchen, bath, garage circuits |
10 AWG | 1.21 Ω | 35 A (30A breaker) | Dryers, water heaters, 12V solar leads |
6 AWG | 0.491 Ω | 65 A | 50A–60A EV chargers, ranges, hot tubs |
2 AWG | 0.194 Ω | 115 A | 100A detached garage / workshop subpanels |
NEC Informational Note 210.19(A) recommends keeping voltage drop to 3% or less on any branch circuit (such as a garage outlet or EV charger) and 5% or less combined for a feeder plus branch circuit.
Enter the one-way distance from the breaker panel or battery bank to the load. For DC and Single-Phase AC circuits, the calculator automatically multiplies by 2 (hot + neutral/return path), and for 3-Phase AC it multiplies by √3 (1.732).
At 12 volts, a 3% drop is only 0.36 volts (compared to 3.6 volts on a 120V circuit)—ten times tighter. Carrying 20 amps over just 25 feet at 12V typically requires 8 AWG or 6 AWG copper wire.
Aluminum has roughly 1.6× higher electrical resistance than copper, so you typically step up two AWG sizes (e.g., 1/0 AWG aluminum instead of 2 AWG copper) to achieve the same ampacity and voltage drop—often at a significantly lower material cost.
Single-Phase AC & DC: Vdrop = (2 × L × I × R) / 1000. Three-Phase AC: Vdrop = (1.732 × L × I × R) / 1000, where L is one-way length in feet, I is current in amps, and R is NEC Chapter 9 Table 8 resistance in ohms per 1,000 feet.
Yes. Always confirm conduit fill, ambient temperature derating, continuous-load 125% rules (like EVSE chargers), and local NEC amendments with a licensed electrician.