Voltage Drop Calculator —
NEC Wire Size (AWG) for AC & DC Runs.

Compute exact voltage drop, delivered load voltage, conductor heat loss, and minimum compliant Copper or Aluminum AWG wire size for 120V/240V branch circuits, subpanels, 3-phase motors, and 12V DC solar/RV runs.

Circuit & Conductor Parameters

12 AWG copper Result
5.79 V drop (4.83%)

UPSIZE RECOMMENDED: Switch to at least 8 AWG copper to stay under 3% voltage drop and within 75°C ampacity.

Voltage at Load
114.2 V
Wire Heat Loss
86.8 W
Min Safe Gauge
8 AWG
Compare Wire Sizes for 15A @ 100 ft (copper)
GaugeDrop (V)Drop (%)75°C AmpsStatus
18 AWG23.31 V19.42%14 AUpsize
16 AWG14.67 V12.22%18 AUpsize
14 AWG9.21 V7.68%20 AUpsize
12 AWG5.79 V4.83%25 AUpsize
10 AWG3.63 V3.02%35 AUpsize
8 AWG2.29 V1.91%50 A✓ Pass
6 AWG1.47 V1.23%65 A✓ Pass
4 AWG0.92 V0.77%85 A✓ Pass
2 AWG0.58 V0.48%115 A✓ Pass
1 AWG0.46 V0.39%130 A✓ Pass
1/0 AWG0.37 V0.30%150 A✓ Pass
2/0 AWG0.29 V0.24%175 A✓ Pass
3/0 AWG0.23 V0.19%200 A✓ Pass
4/0 AWG0.18 V0.15%230 A✓ Pass

NEC WIRE SIZING GUIDE

How to size electrical wire for voltage drop and ampacity.

1. Standard Voltage Drop Formulas

Single-Phase AC & DC: Vdrop = 2 × L × I × R ÷ 1,000. Three-Phase AC: Vdrop = 1.732 × L × I × R ÷ 1,000. Always measure L as one-way conductor run length in feet.

2. Check Both Ampacity & Voltage Drop

A wire must satisfy two checks: safe 75°C thermal ampacity (so insulation never overheats) AND ≤3% branch voltage drop (so motors, EV chargers, and inverters run efficiently).

3. Long Runs & EV Chargers

Continuous 48A EV chargers on a 60A breaker over 75–100 ft frequently benefit from upsizing from 6 AWG to 4 AWG copper to cut continuous heat waste inside walls and conduit.

NEC Copper Wire Resistance & 75°C Ampacity Quick Reference

Wire SizeCopper Resistance (Ω / 1,000 ft)Copper 75°C AmpacityCommon Residential / DC Use
14 AWG3.07 Ω20 A (15A breaker)15A lighting & bedroom receptacles
12 AWG1.93 Ω25 A (20A breaker)20A kitchen, bath, garage circuits
10 AWG1.21 Ω35 A (30A breaker)Dryers, water heaters, 12V solar leads
6 AWG0.491 Ω65 A50A–60A EV chargers, ranges, hot tubs
2 AWG0.194 Ω115 A100A detached garage / workshop subpanels

Frequently Asked Questions

What is the NEC maximum recommended voltage drop percentage?

NEC Informational Note 210.19(A) recommends keeping voltage drop to 3% or less on any branch circuit (such as a garage outlet or EV charger) and 5% or less combined for a feeder plus branch circuit.

Do I enter one-way distance or total round-trip wire length?

Enter the one-way distance from the breaker panel or battery bank to the load. For DC and Single-Phase AC circuits, the calculator automatically multiplies by 2 (hot + neutral/return path), and for 3-Phase AC it multiplies by √3 (1.732).

Why do 12V DC solar and RV runs require much thicker wire than 120V AC?

At 12 volts, a 3% drop is only 0.36 volts (compared to 3.6 volts on a 120V circuit)—ten times tighter. Carrying 20 amps over just 25 feet at 12V typically requires 8 AWG or 6 AWG copper wire.

How does Aluminum wire compare to Copper for long subpanel feeders?

Aluminum has roughly 1.6× higher electrical resistance than copper, so you typically step up two AWG sizes (e.g., 1/0 AWG aluminum instead of 2 AWG copper) to achieve the same ampacity and voltage drop—often at a significantly lower material cost.

What is the voltage drop formula used by this calculator?

Single-Phase AC & DC: Vdrop = (2 × L × I × R) / 1000. Three-Phase AC: Vdrop = (1.732 × L × I × R) / 1000, where L is one-way length in feet, I is current in amps, and R is NEC Chapter 9 Table 8 resistance in ohms per 1,000 feet.

Should I verify local electrical codes before pulling wire?

Yes. Always confirm conduit fill, ambient temperature derating, continuous-load 125% rules (like EVSE chargers), and local NEC amendments with a licensed electrician.