Conduit Fill Calculator —
NEC Chapter 9 & Box Fill 314.16.

Size EMT, PVC Schedule 40/80, RMC, IMC, and FMC conduits with mixed wire gauges, check 3-wire jam ratio, and calculate NEC 314.16 outlet box fill in real time.

Conductors in Raceway

Presets:
NEC Fill Result
17.5%/ 40% max
✓ NEC PASS
0%NEC Limit: 40% (7 wires)100%
Wire Area / Conduit ID
0.0931 / 0.533 in²
Smallest Legal Size
1/2" EMT

NEC CODE REFERENCE

Quick reference for NEC Chapter 9 conduit fill and Table 314.16(B) box fill.

1. The 53% / 31% / 40% Rule

NEC Chapter 9 Table 1 limits fill to 53% for 1 wire, 31% for 2 wires (to prevent side-by-side wedging), and 40% for 3 or more wires. Short nipples (≤ 24") allow 60% fill.

2. Mixed Wire Gauges & Grounds

Add separate rows for phase conductors, neutrals, and reduced-size equipment grounds (THHN, XHHW-2, RHW-2, or Bare Copper). Click Auto to jump straight to the smallest NEC-compliant trade size.

3. NEC 314.16 Outlet Box Sizing

Switch to the Box Fill tab to tally conductors (1× each), internal clamps (1× largest), switches/receptacles (2× largest on yoke), and grounds (1× up to four EGCs + 0.25× each extra).

NEC Table 314.16(B) — Volume Allowance Required per Conductor

Conductor Size (AWG)Free Space in Box (cu in)Free Space (cm³)Typical Circuit Use
14 AWG2.00 cu in32.8 cm³15A lighting & branch circuits
12 AWG2.25 cu in36.9 cm³20A kitchen, bath & general receptacles
10 AWG2.50 cu in41.0 cm³30A dryer, water heater, A/C
8 AWG3.00 cu in49.2 cm³40A–50A range & EV charger
6 AWG5.00 cu in81.9 cm³50A–60A subpanel & EV charger

Frequently Asked Questions

What are the NEC maximum conduit fill percentages?

Under NEC Chapter 9, Table 1, maximum conduit fill is 53% for 1 conductor, 31% for 2 conductors, and 40% for 3 or more conductors. For short conduit nipples 24 inches or less in length (Chapter 9, Note 4), up to 60% fill is permitted.

How do I calculate conduit fill for mixed wire gauges?

Add the cross-sectional area (from NEC Chapter 9, Table 5) of every individual conductor—including neutrals and insulated or bare equipment grounding conductors—then divide that sum by the conduit internal area (Table 4). If the total is 3 or more wires, the ratio must not exceed 40%.

What is the Jam Ratio warning for 3 conductors?

When pulling 3 equal-sized conductors through conduit bends, if the conduit inner diameter divided by conductor outer diameter (× 1.05 for bend ovality) falls between 2.8 and 3.2, the middle wire can wedge between the outer two and lock up the pull.

How does NEC 314.16 box fill count equipment grounding conductors (EGCs)?

Starting with the 2020 and 2023 NEC (314.16(B)(5)), up to four equipment grounding conductors count as a single volume allowance based on the largest EGC in the box, plus 0.25 volume allowance for each additional EGC beyond four.

Do pigtails inside an outlet box count toward NEC 314.16 box fill?

No. Conductors that originate and terminate entirely within the box—such as short grounding or neutral pigtails—do not count toward box fill volume.

How many volume allowances does a switch or receptacle take?

Each mounting yoke or strap containing one or more switches or receptacles counts as 2 volume allowances based on the largest conductor connected to that device.